AC/DC Digital Clamp Meters


2009A
 

True RMS reading instrument ideal for accurate measurement of distorted waveforms and non-sinusoidal waveforms arising from thyristors.
Can measure AC and DC currents up to 2000A.
Output terminal for connection to recorders.


2009A
CE

 
AC A 400A (True RMS)
|±1.5%rdg±3dgt [50/60Hz]
|±3%rdg±4dgt [30Hz~1kHz]
2000A (150~1700A)(True RMS)
|±1.5%rdg±2dgt [50/60Hz]
|±3%rdg±4dgt [30Hz~1kHz]
2000A (1701~2000A)(True RMS)
|±3.5%rdg±3dgt [50/60Hz]
AC V 40/400/750V (True RMS)
|±1.5%rdg±3dgt [50/60Hz]
|±2%rdg±4dgt [30Hz~1kHz]
DC A 400/2000A ±1.5%rdg±2dgt
DC V 40/400/1000V ±1%rdg±2dgt
Ω 400/4000Ω|±1.5%rdg±2dgt
Continuity buzzer buzzer sounds below 20Ω
Frequency 10 ~ 4000Hz ±1.5%rdg±5dgt
Output Voltage 400/2000A DC400mV/200mV
Conductor Size Ø55mm max.
Safety Standard
IEC61010-1 CAT.III 600V
CAT.II 1000V
IEC61010-2-031
IEC61010-2-032
Frequency Response 40Hz~1kHz
Withstand Voltage 5550V AC for 1 minute
Power Source 6F22(9V) × 1
Dimensions 250(L) × 105(W) × 49(D)mm
Weight 540g approx.
Accessories 7107(Test Leads)
8201(Output Plug)
9094(Carrying Case)
6F22 × 1
Instruction Manual
Optional 8004/8008(Multi-Tran)(AC only)
7014(Output Cord)


       For more information, please contact ExpotechUSA       
       Shipping Address                  Mailing Address                           Phone                   Web     
10700 Rockley Road
10700 Rockley Road
281-496-0900 [voice] Click here to e-mail us
Houston, Texas 77099
Houston, Texas 77099
281-496-0400 [fax]   
  ExpotechUSA's HomePage