| Continuity
Testing |
| Measuring
Ranges |
20/200/2000Ω Autoranging |
| Open
Circuit Voltage |
>6V |
| Short
Circuit Current |
>200mA
DC |
| Accuracy |
|±(1.5%rdg+3dgt) |
| Loop
Impedance Testing |
| Rated
Voltage |
230V
AC ±10% [50Hz] |
| Voltage
Measuring Range |
100~400V
AC [50Hz] |
| Impedance
Ranges |
20/200/2000Ω |
| Nominal
Test Current |
25A
(20Ω range) 1.2A (200Ω range) 1.2A (2000Ω range) |
| Test
Period |
1/2
cycle (10ms) |
| Base
Accuracy |
20Ω
range
|±(2%rdg+2dgt)
D-LOK OFF
|±(5%rdg+5dgt)
D-LOK ON |
| RCD
Testing |
| Rated
Voltage |
230V
AC ±10% [50Hz] |
| Trip
Current Settings |
RCD
× 1/2 : 10,30,100,300,500,1000mA
RCD × 1 : 10,30,100,300,500,1000mA
RCD × 5 : 10,30,100mA |
| Trip
Current Duration |
RCD
× 1/2 × 1: 2000ms
RCD × 5: 200ms fast trip 50ms |
| Accuracy |
Trip
current +10%-0%
of test current at 230V Trip time±(2%rdg + 3dgt) |
| Insulation
Testing |
| Measuring
Ranges |
20/200/2000MΩ
Autoranging |
| Test
Voltage |
250V,
500Vand 1000V DC |
Output
Voltage on
Open Circuit |
250V+20%-0%
500V+20%-0%
1000V+20%-0% |
| Rated
Current |
>1mA |
| Accuracy |
0~100MΩ|±(2%rdg+3dgt)
100MΩ~2000MΩ|±(5%rdg+4dgt) |
| PSC
Testing |
| Rated
Voltage |
230V
AC ±10% [50Hz] |
| PSC
Ranges |
2000A
and 20kA |
| Accuracy |
PSC
accuracy derived from measured
loop impedance specification and measured
voltage specification |
| Fault
Current |
| Rated
Voltage |
230V
AC ±10% [50Hz] |
| Fault
Current Ranges |
2000A
and 20kA |
| Nominal
Test Current |
1.2A(2000A)
25A(20kA) |
| Accuracy |
Fault
Current accuracy derived from measured loop impedance specification and
measured voltage specification |
| Earth
Resistance |
| Ranges |
20Ω/200Ω/2000Ω |
| Output
Voltage |
50V
peak to peak square wave |
| Frequency |
720Hz
±5% |
| Accuracy |
20Ω|±(2%rdg+5dgt)
200/2000Ω|±(2%rdg+3dgt) |
| General |
| Safety
Standard |
IEC61010-1
CAT.III 300V Pollution Degree 2
IEC61557 |
| Withstand
Voltage |
3700V
AC for 1 minute |
| Power
Source |
8
× 1.5V R6 or LR6 |
| Dimensions |
105(L)
× 210(W) × 240(D)mm |
| Weight |
1924g
approx. |
| Accessories |
| 7098
|
(Distribution
board test leads for Loop/PSC/RCD testing ) |
| 7099
|
(Moulded
plug test leads(1 set) for Loop and RCD testing at sockets(EU plug) )* |
7025 (Lead for insulation and continuity testing)
7109 (Earth resistance test leads (1 set))
KSLP5 (external earth probe)
8032 (auxiliary earth spikes)
8210 (IrDA Adaptor)
Durable Holdall
Accessory pouch
Battery 8 × 1.5V R6 or LR6
Instruction Manual |