| Range |
Insulation
resistance |
Voltage
measurement |
| 500V |
1000V |
2500V |
5000V |
AC/DC V |
| Measuring
range |
0.0~99.9MΩ
100~999MΩ |
0.0~99.9MΩ
100~999MΩ
1.00~1.99GΩ |
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ |
0.0~99.9MΩ
100~999MΩ
1.00~9.99GΩ
10.0~99.9GΩ
100~1000GΩ
(1TΩ) |
30~600V
AC/DC
[50/60Hz] |
| Accuracy |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt |
|±5%rdg |±3dgt
|±20%(100GΩ or
more) |
|±2%rdg |±3dgt |
| Short
Circuit Current |
1.3mA approx. |
------- |
| Rated
test Current |
1mA to1.2mA
at 0.5MΩ load |
1mA to1.2mA
at 1MΩ load |
1mA to1.2mA
at 2.5MΩ load |
1mA to1.2mA
at 5MΩ load |
------- |
| Open
circuit voltage |
500VDC
|
1000VDC
|
2500VDC
|
5000VDC
|
------- |
| Maximum
display |
999 Counts (1000 counts only at 1000GΩ) |
630
Counts |
| Current
consumption |
About 1000mA (During measurement) |
25mA
approx. |
Withstand
Voltage
Safety standard |
5320V AC for 5 seconds
IEC 61010-1 CAT.III 600V, pollution Degree 2 |
| Power
supply |
DC12V : R14×8 |
| Dimensions |
205(L) × 152(W) × 94(D)mm |
| Weight |
1.8kg approx. |
| Accessories |
7165(Line Probe)
7166(Earth Cord)
7167(Guard Cord)
8019(Pickle Type Prod)
9124(Hard Carrying Case)
LR14×8pcs(Alkaline Battery Size)
Instruction Manual |
| Optional |
8302(Adaptor for recorder) 7168(Line Probe) |