| Insulation
resistance |
| Test
voltage |
100V |
250V |
500V |
1000V |
Measuring
range
(Auto range) |
4.000/40.00/
200.0MΩ |
4.000/40.00/400.0/2000MΩ |
| First
Effective Measuring range |
0.1~20MΩ |
0.1~40MΩ |
0.1~200MΩ |
0.1~1000MΩ |
| Mid-scale
value |
5MΩ |
50MΩ |
| Accuracy |
|±(2%rdg+6dgt) |
| Second
effective measuring range lower |
0~0.099MΩ |
| Second
effective measuring range upper |
20.01~
200.0MΩ |
40.01~
2000MΩ |
200.1~
2000MΩ |
1001~
2000MΩ |
| Accuracy |
|±(5%rdg+6dgt) |
| Rated
current |
DC
1~1.2mA |
| Output
short circuit current |
1.5mA
max |
| Ω/Continuity |
| Auto
range |
40.00/400.0Ω |
| Accuracy |
|±(2%rdg+8dgt) |
| Output
Voltage on open circuit |
5V±20% |
| Output
short circuit current |
DC
220±20mA |
| Fuse |
Quick
acting ceramic fuse 0.5A/600V(Ø6.35×32mm) |
| AC
Voltage |
| Range |
AC
20~600V(50/60Hz)
DC -20~-600V/+20~+600V |
| Accuracy |
|±(3%rdg+6dgt) |
| General |
| Other
function |
Data
hold, Zero Ω ADJ., Auto discharge, Bar graph display, Memory,
Comparator, Live circuit warning, Auto power off,
Battery alarm, Backlight, Safety lock, Remote measurement,
Measurement button lock(Continuous measurement) |
| Safety
standard |
IEC/EN
61010-1 : 2001 CAT.III 600V IEC/EN 61557-1,2,4 |
| EMC
standard |
IEC/EN
61326-1 (CE marking) |
| IP
rating |
IP40 |
| Dimensions
/ Weight |
105(L)
× 158(W) × 70(D)mm / 600g approx. |
| Power
source |
R6P×6
or LR6×6 |
| Accessories |
7103(Test
lead with remote control switch),
7131(Safety crocodile clip), 7161(Test bar), 8017(Extension prod),
9120(Cord case), 9121(Shoulder strap), R6P(AA)×6,
Instruction Manual |
| Optional |
7115(Extension
Probe), 8016(Pickel Type Prod),
9089(Carrying Case) |